占位边距

Products

Integrate the full range of core products, covering energy storage, charging piles, power protection, and other fields, providing detailed specifications and technical parameters

Large-Capacity High-Speed Current-Limiting Circuit Breaker
  • Large-Capacity High-Speed Current-Limiting Circuit Breaker
Key attributes
Brand Rw Energy
Model NO. Large-Capacity High-Speed Current-Limiting Circuit Breaker
Rated voltage 24kV
Rated normal current 100A
Rated frequency 50/60Hz
Series DGK
Product descriptions from the supplier
Description

Product Introduction

  • The DGK is mainly applied in low-current systems, with a rated current of <630A and a rated breaking current of ≤200kA.

  • The DGK can complete current limiting and interrupt short-circuit current within 10ms, ensuring that the actual current present in the fault circuit is only 15~50% of the expected short-circuit current.

  • TXB3 = DGK + switchgear cabinets with different configurations. The TXB3 is assembled by connecting the DGK in series with general-purpose switchgear such as vacuum circuit breakers, load switches, or disconnectors. For normal switching operations and operations involving load current or overload current, these are performed via the switchgear (load switches or circuit breakers) integrated in the TXB3 device.

  • This product not only achieves low-cost interruption of short-circuit current but also eliminates the need to upgrade the dynamic and thermal stability parameters of relevant electrical equipment in branch circuits. Thus, it realizes rational circuit design and reduces the investment cost of project equipment.

Product Features and Benefits

  • Fast breaking speed (high speed), the whole breaking time is less than 10ms

  • The opening process has obvious current limiting characteristics (current limiting)

  • It is mainly used in small rated current systems

  • According to the needs of the project, the non-standard cabinet type is assembled, and there are a variety of configuration schemes

  • Reduce the cost of a large number of substation replacements of switches and other main equipment

Main technical parameters

serial number

Parameter Name

unit

Technical parameters

1

Rated voltage

kV

3.6~24

2

Rated current

A

6.3~500

3

Rated expected short-circuit breaking current

kA

20-120

4

Current limit coefficient = cut-off current / expected short-circuit current peak

%

15~50

5

Insulation level

Power frequency withstand pressure

       kV/1min

42/48

Lightning impact withstand pressure

            kV

75/85kV

Product Usage

  • Fast short-circuit protection of power branch bus in hydropower plants, limiting and quickly interrupting high-amplitude short-circuit current, avoiding the use of expensive generator circuit breakers, and improving technical economy

  • Large synchronous motor outlet

  • For fast breaking and rapid isolation of fault points in feeders prone to short circuit faults

 

Related Products
Related Solutions
Send inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
Chat
Manager